NYSDOT Federal Aid Notification Croton-on-Hudson
document
6 pages
Meeting: portal event 984 (no meeting page on file)
Agenda item: Referral from Village Board for a Local Waterfront Revitalization Program (LWRP) Consistency review for NYS Project F-2024-0476: New York State Department of Transportation-federal funding for cleaning/washing bridges and sealing decks U.S. Route 9 bridges over New York State Route 129
Document, 6 pages. Attached to agenda item: “Referral from Village Board for a Local Waterfront Revitalization Program (LWRP) Consistency review for NYS Project F-2024-0476: New York State Department of Transportation-federal funding for cleaning/washing bridges an”
Retrieved 2026-04-15 from the village's meeting portal.
View the original PDF ↗
Also attached to this agenda item:
F-2024-0476 Croton-on-Hudson LWRP Memo
LWRP 2024 Updated2
Extracted text
50 Wolf Road, Albany, NY 12232 │ www.dot.ny.gov
July 18, 2024
VIA EMAIL
Jennifer Street
Supervisor, Consistency Review Unit
Division of Coastal Resources
New York State Department of State
99 Washington Avenue, Suite 1010
Albany, NY 12231
CR@dos.ny.gov; Jennifer.Street@dos.ny.gov
RE:
PIN 8815.93
BRIDGE WASHING & DECK SEALING
VARIOUS MUNICIPALITIES
COLUMBIA, DUTCHESS, PUTNAM, WESTCHESTER, ROCKLAND, ORANGE,
AND ULSTER COUNTIES
Dear Ms. Street:
The New York State Department of Transportation (NYSDOT) is progressing a project
with locations within the designated New York State Coastal Zone Management Area
(CZMA); several locations are within the limits of Local Waterfront Revitalization
Program (LWRP) areas, Scenic Area of Statewide Significance (SASS), and Significant
Coastal Habitats. Attached is a location map. A GIS shapefile or Google Earth KMZ file
of the locations is available upon request. This letter serves as Federal Aid Notification.
The project will consist of cleaning/washing bridges and sealing decks as needed to
remove debris and protect against corrosive substances. This project is part of the
Regional annual bridge washing/deck sealing program which requires that each
structure be cleaned, and concrete bridge decks be sealed periodically. All work will
occur within the existing highway right-of-way, there will be no excavation, and there will
be no changes to the bridges.
The project will comply with the policies of the CZMA Program and the LWRP areas.
The project is federally funded through the Federal Highway Administration. No federal
permits are required. The project is being progressed as a NEPA Class II action and
SEQRA Type II action in accordance with the Department’s implementing the
regulations of SEQR (17 NYCRR Part 15).
Based on the above and enclosed information, we respectfully request that NYSDOS
render a general concurrence decision regarding the release of federal funding in support
of the project. If you have any questions or would like to discuss the project in more
detail, please contact me at Stephanie.Lewison@dot.ny.gov or (845) 431-5823.
Stephanie Lewison
Regional Environmental Contact
Attachment:
Project Location Map
ec:
Eric Foster, Project Manager, NYSDOT Region 8
Sources: Esri, HERE, Garmin, USGS, Intermap, INCREMENT P, NRCan, Esri
Japan, METI, Esri China (Hong Kong), Esri Korea, Esri (Thailand), NGCC, (c)
OpenStreetMap contributors, and the GIS User Community
±
0.25
0.5
0.125
Miles
1 inch = 1,176.88 feet
NYSDOT PIN 8815.93
BRIDGE WASHING & DECK
SEALING
VARIOUS MUNICIPALITIES
COLUMBIA, DUTCHESS, PUTNAM,
WESTCHESTER, ROCKLAND,
ORANGE, AND ULSTER COUNTIES
8/13/2024
Project locations
Coastal Zone Mgmt Area Boundary
Local Waterfront Revitalization Program Area
Scenic Areas of Statewide Significance
Significant Coastal Fish and Wildlife Habitats
559-1.01
NEW YORK STATE DEPARTMENT OF TRANSPORTATION
Sections 200 - 599 STANDARD SPECIFICATIONS (USC) September 1, 2024 Volume 2
559-1 DESCRIPTION. The work in this section shall include work required for protective coatings of
concrete.
559-1.01 Scope. Apply a protective sealer to concrete surfaces to slow down/reduce the ingress of water
and chlorides into the concrete at locations indicated on the plans or as directed by the Engineer.
559-1.02 Definitions
A. Penetrating Type Protective Sealers – A Penetrating Sealer is a type of sealer that is applied to a
concrete surface and has the ability to penetrate the surface and chemically bond to the concrete.
These are used on both new and existing concrete bridge decks and traffic bearing surfaces to include,
but not limited to: approach slabs, bridge deck overlays, and sidewalks. Penetrating Sealers are also
used on new structural concrete and precast concrete elements that are subject to water and/or
chloride exposure and require long term protection.
B. Coating Type Protective Sealers – A Coating Sealer is a type of sealer that is applied to the
surface of existing concrete when a uniform appearance is required. These are two part systems which
consist of a primer coat followed by a top coat. Coating Sealers are used on new and existing concrete
surfaces when an aesthetic appearance is desired, as they can hide stained or underlying repair areas
while providing protection to the concrete.
559-2 MATERIALS
559-2.01 Protective Sealing of Structural Concrete
The protective sealers to be used on concrete surfaces shall be on the Approved List and meet the
requirements of one of the following subsections:
§717-03
Penetrating Type Protective Sealers
§717-04
Coating Type Protective Sealers
The protective sealer required for use on all traffic and/or pedestrian bearing surfaces shall be a
Penetrating Type Protective Sealer which has a 100% solids content as noted on the Approved List.
Penetrating Type Protective Sealer manufactured after April 1, 2022 shall be tinted with a fugitive dye
such that the sealer is readily distinguishable upon the concrete surface for at least 4 hours after
application but shall become inconspicuous within 7 days after application.
559-3 CONSTRUCTION DETAILS
559-3.01 Protective Sealing of Structural Concrete
A. General. Provide the Engineer with the Sealer Manufacturer's written instructions for application
and the proposed method of surface preparation and sealer application at least 7 days prior to the start
of work. Only one brand and specific type of sealer off the Approved List will be allowed for use on
each individual element of a project (i.e., each pier, bridge deck, abutment, etc.). Follow all sealer
manufacturer’s written instructions except as modified herein.
B. Surface Preparation. For both new and existing concrete applications, care shall be taken while
preparing and cleaning the surfaces to be sealed to ensure that all contaminants are satisfactorily
removed without undue damage to the concrete surface or exposure of coarse aggregate.
559-3.01
NEW YORK STATE DEPARTMENT OF TRANSPORTATION
Sections 200 - 599 STANDARD SPECIFICATIONS (USC) September 1, 2024 Volume 2
Contaminants may include but not be limited to grime, dirt, laitance, efflorescence, curing
compounds, standing water, oil, paint, or other foreign particles which may prevent penetration or
adhesion of the sealer. Prepare the surface for sealing by utilizing a procedure with appropriate
equipment that will satisfactorily complete this work, in accordance with the sealer manufacturer’s
written instructions and subject to the approval of the Engineer. Surface preparation methods usually
consist of either: sand, shot, or water blasting with a minimum water blast pressure of 7,000 psi.
Upon completion of the cleaning process, the concrete surface shall be free of any remaining residue.
All surface preparation work shall be completed and approved by the Engineer, prior to sealer
application.
1. New Bridge Decks and Bridge Deck Overlays. All required surface texturing, saw cut
grooving, diamond grinding, and construction of barriers, parapets, and walks shall be completed
prior to the surface being prepared for sealing. All new concrete bridge decks and bridge deck
overlays to be sealed shall air dry for a minimum of 72 hours after completion of the required
curing period. If the concrete is subjected to rain or moisture from other operations, the drying
period shall be extended 24 hours from the time that the concrete has stopped being wetted. After
the drying period has ended, the concrete surface shall be lightly cleaned in accordance with the
sealer manufacturer’s written instructions followed by vacuum cleaning to prepare the surface
and remove any contaminants or loose particles. If water blasting is utilized, the surface shall be
air dried upon completion for a minimum of 24 hours or as specified in the sealer manufacturer's
written instructions, whichever is longer, before the sealer can be applied. The deck shall be
clean and free of all debris prior to sealer application. If a new bridge deck or bridge deck
overlay is subjected to traffic for 21 days or more prior to sealing, the concrete surface shall be
thoroughly cleaned in accordance with the sealer manufacturer's written instructions before sealer
can be applied.
2. New Structural Concrete. All new structural concrete that is to be sealed shall air dry for 14
days after completion of the required curing period or for the length of time specified in the sealer
manufacturer's written instructions, whichever is longer. If the concrete is subjected to rain or
moisture from other project operations, the drying period shall be extended 24 hours for every
day the concrete is subjected to water. After the drying period has ended, the concrete surface
shall be lightly cleaned in accordance with the sealer manufacturer's written instructions followed
by vacuum cleaning, to prepare the surface and remove any contaminants or loose particles. If
water blasting is utilized, the surface shall be air dried upon completion for a minimum of 24
hours or as specified in the sealer manufacturer's written instructions, whichever is longer, before
the sealer can be applied. The concrete surface shall be clean and free of all debris prior to sealer
application.
3. Existing Structural Concrete and Existing Bridge Decks. Existing concrete surfaces to be
sealed shall be thoroughly cleaned with light sand or shot blasting, in accordance with the sealer
manufacturer's written instructions followed by vacuum cleaning, to prepare the surface and
remove any contaminants or loose particles. Where the use of sand or shot blasting is prohibitive,
water blasting may be allowed, provided the Contractor can demonstrate the ability to provide a
clean, porous surface in accordance with the requirements of the sealer manufacturer’s written
instructions. If the concrete is subjected to rain or moisture from other operations such as water
blasting, upon completion the surface shall be air dried for a minimum of 24 hours or as specified
in the sealer manufacturer's written instructions, whichever is longer, before the sealer can be
applied. Surface preparation of any concrete or bridge deck surfaces with existing coatings known
to be asbestos containing shall be performed subsequent to coating removal and completed in
accordance with Section 210 of the Standard Specifications.
559-3.01
NEW YORK STATE DEPARTMENT OF TRANSPORTATION
Sections 200 - 599 STANDARD SPECIFICATIONS (USC) September 1, 2024 Volume 2
C. Sealer Application
1. Weather Limitations. Sealer materials shall not be applied during wet weather conditions or
when adverse weather conditions are anticipated within 12 hours of the completion of sealer
application or as specified in the sealer manufacturer's written instructions, whichever is longer.
Ambient and surface temperatures shall be a minimum of 40°F and rising during application until
the sealed concrete is dry to the touch. Application by spray methods will not be permitted during
windy conditions if unsatisfactory coverage will result.
2. Yield Check. If penetrating sealer is to be applied in a single coat to a traffic bearing surface,
the Contractor shall demonstrate to the satisfaction of the Engineer that the proposed equipment
and procedure will result in uniform coverage at the application rate specified on the Approved
List before sealer can be applied.
3. Application. The protective sealer shall be used as supplied by the manufacturer without
thinning or alteration with exception of the fugitive dye. Equipment for sealer application shall be
compatible with sealer manufacturer requirements, in good working order, clean of foreign
materials and approved for use by the Engineer. The quantity of sealer material delivered to the
project shall be demonstrated by direct measurement in the presence of the Engineer prior to
commencement of sealing application. Assumptions of volumes of unopened containers will not
be permitted. The sealer shall be applied by brushing, spraying, or rolling, as recommended by
the sealer manufacturer. The direct measurement shall be repeated in the presence of the
Engineer when sealer application work is complete to verify the quantity of sealer applied.
a. For Penetrating Type Protective Sealers – Apply sealer in one or more coats in accordance
with the sealer manufacturer’s written instructions. The total quantity of sealer applied by all
coats shall be equal to the quantity required at the application rate specified on the Approved
List. The application rate for all traffic and pedestrian bearing surfaces shall be 200 ft2/gal.
Additional coats shall be applied perpendicular to the previous coat. Care shall be taken when
applying each coat, such that running or pooling does not occur. The final coat shall be
allowed to dry according to the sealer manufacturer's written instructions before opening to
traffic. On sloping and vertical concrete surfaces, sealer application shall progress from
bottom to top. Care shall be taken to ensure that the entire surface of the concrete is covered,
and all pores filled.
A 1-pint sample of sealer is required to be taken at a random time during sealer
application from the point of application (i.e., from the nozzle of sprayer or spray bar or from
the sealer container where sprayers, brushes or rollers are loaded) for quality assurance
purposes. This sample shall be submitted to the Department’s Central Testing Laboratory
(CTL), to the attention of the Chemistry Lab for evaluation. Additional samples may be
requested by the Department at any time.
b. For Coating Type Protective Sealers – Apply in accordance with the Contract Plans and
the sealer manufacturer's written instructions.
559-4 METHOD OF MEASUREMENT
The quantity to be measured for payment will be in the number of square feet of concrete sealed measured
to the nearest whole square foot.
559-5 BASIS OF PAYMENT